Mfg Part Number
9020-0376

BINDER MK240-400V Series MK - Dynamic Climate Chambers, For Rapid Temperature Changes, 9020-0376

Quick Overview

Average cooling down time according to IEC 60068-3-5 [K/min]: 4.5
Average heating-up rate according to IEC 60068-3-5 [K/min]: 5
Cooling down time from 180 °C to -40 °C [min]: 110
Max. heat compensation at 25 °C [W]: 2000
Temperature fluctuation depending on setpoint [± K]: 0.1…0.5
Temperature range: -40…180
Temperature variation depending on setpoint [± K]: 0.1…1.2

$38,999.25
Order will ship within 1-3 business days
Add to Wish List






Benefits

Homogeneous climate conditions thanks to APT.line™ technology
Comprehensive programming and data acquisition
Large heated viewing window

Important characteristics

Temperature range: -40 °C to +180 °C
APT.line™ preheating chamber technology
Programmable condensation protection for test material
Heated viewing window with LED interior lighting
BINDER Multi Management Software APT-COM™ Basic Edition
Troubleshooting system with visual and audible alarms
Intuitive touchscreen controller with time-segment and real-time programming
Internal data logger, measured values can be read out in open format via USB
Access port with silicone plug, 50 mm, left
Class 2 independent adjustable temperature safety device (DIN 12880) with visual alarm
4 castors, two with brakes
Computer interface: Ethernet
Adjustable ramp function
Integrated chart recorder
Real-time clock
Door heating
1 stainless steel rack
Inner chamber made of stainless steel
CFC-free refrigerant R-452A
Cooling with compressor cooling unit

Optional equipment

APT-COM Multi Management Software – for managing, recording, and documenting unit parameters
Racks – option of stainless steel racks, depending on test requirements
Compressed air supply system
Services – wide range of services to ensure that the unit functions correctly

Technical specifications

Performance Data Temperature:

Average cooling down time according to IEC 60068-3-5 [K/min]: 4.5
Average heating-up rate according to IEC 60068-3-5 [K/min]: 5
Cooling down time from 180 °C to -40 °C [min]: 110
Max. heat compensation at 25 °C [W]: 2000
Temperature fluctuation depending on setpoint [± K]: 0.1…0.5
Temperature range: -40…180
Temperature variation depending on setpoint [± K]: 0.1…1.2

Electrical data


Nominal power [kW]: 5.6
Phase (Nominal voltage): 3~
Power frequency [Hz]: 50
Rated Voltage [V]: 400
Unit fuse [A]: 16

Doors

Unit doors: 1

Housing dimensions not incl. fittings and connections

Depth net [in]: 36.45
Height net [in]: 67.4
Width net [in]: 43.9

Internal Dimensions

Depth [in]: 17.45
Height [in]: 27.58
Width [in]: 28.96

Measures


Interior volume [cu.ft.]: 8
Load per rack [lbs]: 66
Net weight of the unit (empty) [lbs]: 750
Permitted load [lbs]: 154
Viewing window height [in]: 11.82
Viewing window width [in]: 20.02
Wall clearance back [in]: 11.82
Wall clearance sidewise [in]: 7.88

Environment-specific data


Energy consumption at 20 °C: 1300 Wh/h
Sound-pressure level [dB(A)]: 62

Fixtures


Number of shelves (std./max.): 1/6

More Information
Brand BINDER
UNSPSC 41103416